Monitoring of Air Infiltration in Museums, Case study: The National Museum of Fine Arts, Stockholm, Sweden
Högskolan i Gävle, Institutionen för teknik och byggd miljö, Ämnesavdelningen för inomhusmiljö. (Ventilation och Luftkvalité)
2004 (engelsk)Inngår i: The 6th Indoor Air Quality Meeting: Padova, Italy, 2004Konferansepaper, Publicerat paper (Annet vitenskapelig)
Abstract [en]

This paper describes tracer gas measurements at the National Museum of Fine Arts in Stockholm. The building was erected 1850-1860 and the architect was Friedrich August Stüler. He created several museums of Fine Arts, among them Neues Museum in Berlin. The museum building in Stockholm has a volume of almost 90 000 m3 and the number of registered objects of art is well over 600 000. The collection includes one of the world’s most prestigious collections of drawings and graphical prints. In this case study the aim was to determine the infiltration through the main entrance and stairwell, through windows and outside walls. The measurement technique used was the Homogeneous Emission Technique added with a 2-zone set up, by using two different tracer gases. Several interesting results were obtained. One result was that more airtight entrance doors would decrease the infiltration into the main stairwell with 40 %. Another result of interest was that the very dry outdoor air was mixed with the indoor air quickly, and that the

mechanical ventilation system with filters and humidifying units has to be upgraded to compensate for the outdoor air infiltration.

sted, utgiver, år, opplag, sider
2004.
Identifikatorer
URN: urn:nbn:se:hig:diva-929OAI: oai:DiVA.org:hig-929DiVA, id: diva2:117591
Konferanse
The 6th Indoor Air Quality Meeting, Padova 10-12 Nov 2004
Tilgjengelig fra: 2007-12-04 Laget: 2007-12-04 Sist oppdatert: 2018-03-13bibliografisk kontrollert

Open Access i DiVA

Fulltekst mangler i DiVA

Andre lenker

http://www.isac.cnr.it/iaq2004/

Personposter BETA

Stymne, Hans

Søk i DiVA

Av forfatter/redaktør
Stymne, Hans
Av organisasjonen

Søk utenfor DiVA

GoogleGoogle Scholar

urn-nbn

Altmetric

urn-nbn
Totalt: 63 treff
RefereraExporteraLink to record
Permanent link

Direct link
Referera
Referensformat
  • apa
  • harvard-cite-them-right
  • ieee
  • modern-language-association-8th-edition
  • vancouver
  • Annet format
Fler format
Språk
  • sv-SE
  • en-GB
  • en-US
  • fi-FI
  • nn-NO
  • nn-NB
  • de-DE
  • Annet språk
Fler språk
Utmatningsformat
  • html
  • text
  • asciidoc
  • rtf