Numerical investigation of Air Change Effectiveness in an Office Room with Impinging Jet Ventilation
University of Gävle, Faculty of Engineering and Sustainable Development, Department of Building, Energy and Environmental Engineering, Energy system. (Energisystem)ORCID iD: 0000-0003-2023-689x
University of Gävle, Faculty of Engineering and Sustainable Development, Department of Building, Energy and Environmental Engineering, Energy system.ORCID iD: 0000-0003-3877-6827
RISE Research Institutes of Sweden, Division of Built Environment - Energy and circular economy, Borås, Sweden.
2018 (English)In: Proceedings of the 4th international Conference on Building Energy & Environment / [ed] K. Inthavong*, C.P Cheung, G. Yeoh, J.Y. Tu, Melbourne: Conference On Building Energy & Environment - COBEE2018, Melbourne Australia , 2018, p. 641-646Conference paper, Published paper (Refereed)
Abstract [en]

Providing occupant comfort and health with minimum use of energy is the ultimate purpose of heating, ventilating and air conditioning systems. This paper presents the air-change effectiveness (ACE) within a typical office room using impinging jet ventilation (IJV ) in combination with chilled ceiling (CC) under different heat loads ranging from 6.5 - 51 W per square meter floor area. In this study, a validated CFD model based on the v2f turbulence model is used for the prediction of air flow pattern and ACE. The interaction effect of chilled ceiling and heat sources results in a complex flow with air circulation. The thermal plumes and air circulation in the room result in a variation of ACE within the room but also close to the occupant. For all studied cases, ACE is above 1.2 close to the occupants, indicating that IJV is more energy efficient than mixing ventilation.

Place, publisher, year, edition, pages
Melbourne: Conference On Building Energy & Environment - COBEE2018, Melbourne Australia , 2018. p. 641-646
Keywords [en]
Impinging jet ventilation
National Category
Energy Engineering
Research subject
Sustainable Urban Development
Identifiers
URN: urn:nbn:se:hig:diva-26567ISBN: 978-0-646-98213-7 (print)OAI: oai:DiVA.org:hig-26567DiVA, id: diva2:1205825
Conference
COBEE2018, 4th international Conference on Building Energy & Environment,5-9 February 2018, Melbourne, Australia
Available from: 2018-05-15 Created: 2018-05-15 Last updated: 2021-02-17Bibliographically approved
In thesis
1. On the performance of stratified ventilation
Open this publication in new window or tab >>On the performance of stratified ventilation
2018 (English)Doctoral thesis, comprehensive summary (Other academic)
Abstract [en]

People nowadays spend most of their time indoors, for example in their homes, cars, in trains, at work, etc. In Sweden, the energy demand in the built environment is a growing issue. The building sector accounts for 40% of total energy use and 15% of total CO2 emissions, and around one-third of the energy use in the world is related to providing a healthy and good comfort indoors. To achieve acceptable indoor climates new designs for the ventilation systems have been proposed in recent decades, among them stratified ventilation systems.

Stratified ventilation is a concept that often allows good performance for both indoor air quality and thermal comfort. Stratified ventilation systems are effective in reducing cross contamination, since there is virtually no mixing in the space; the temperature and the pollutant concentration increase linearly from the heat source with the height of the occupied zone. There are many different ventilation supply devices using the stratified principle, such as displacement supply device (DSD), impinging jet supply device (IJSD) and wall confluent jet supply device (WCJSD).

The main aim of this thesis is to analyze and compare different supply devices based on stratified ventilation, with different setups, related to thermal indoor climate, energy efficiency and ventilation efficiency. The ultimate goal is to contribute to an increased understanding of how ventilation systems with stratified supply devices perform.

Two scientific methods have mainly been used in this thesis, i.e., experimental and numerical investigations. For numerical experiments the CFD (Computational Fluid Dynamics) code ANSYS and FIDAP have been used. Experimental studies have been performed with thermocouples, Hot-Wire Anemometry (HWA) and Hot-Sphere Anemometry, thermal comfort measurement equipment and tracer gas measurement equipment.

This thesis mainly focuses on three research questions: Interaction between a supply device based on stratified ventilation and downdraft from windows; Flow behavior, energy performance and air change effectiveness for different supply devices based on stratified ventilation; and Thermal comfort for different supply devices based on stratified ventilation.

Research question one showed that the arrangement of displacement supply device and window in cold climate has significant effect on the flow pattern below the window. Different supply airflow rates have an effect on both the velocity and the temperature of the downdraft. In this case the velocity decreased by approximately 9.5% and the temperature in the downdraft decreased 0.5°C when the flowrate from the supply device increased from 10 to 15 l/s.

Research question two showed that airflow patterns between different air supply systems were essentially related to characteristics of air supply devices, such as the type, configuration and position, as well as air supply velocities and momentum. For WCJSD, IJSD and DSD, positions of heat sources (such as occupant, computers, lights and external heat sources) played an important role in formation of the room airflow pattern. One interesting observation is that the temperature in the occupied zone is lower and a more stratified temperature field implies a more efficient heat removal by a stratified air supply device. The results revealed that the lowest temperature in the occupied zone was achieved for DSD, but with IJSD and WCJSD slightly warmer, while the system with a mixing supply device (MSD) showed a much higher temperature. The results confirm that air change effectiveness (ACE) for the DSD, WCJSD and IJSD is close to each other. However, MSD shows lower ACE in all the present papers than IJSD, WCJSD and DSD.

Research question three showed that ventilation systems with stratified supply devices in almost all of the studied cases showed an acceptable level for predicted percentage dissatisfied (PPD), predicted mean vote (PMV) and percentage dissatisfied due to draft (DR). If comparing ventilation systems, using IJSD, WCJSD or DSD with MSD always showed thermal comfort better or at the same level.

Abstract [sv]

Människor spenderar en stor del av sin tid inomhus, exempelvis i sina bostäder och bilar, på tåg och på arbetet. Sveriges energibehov i den byggda miljön har en växande trend. Byggnadssektorn står för 40 % av det totala energibehovet och för 15 % av CO2 utsläppet och för cirka en tredjedel av energianvändningen i världen för att tillhandahålla en hälsosam och bra inomhusmiljö. För att skapa en bra inomhusmiljö har nya sätt att ventilera inomhusmiljön utvecklats under de senaste årtiondena. De olika principer som används för att ventilera en byggnad kan indelas i: kolvströmning, omblandande strömning och deplacerande strömning. De genererar rumsförhållanden som ger olika fördelning av hastighet, temperatur och föroreningar i det ventilerade utrymmet.

Stratifierad ventilation är ett koncept som ofta ger ett bra utfall av både inomhusluftkvalitet och termisk komfort. Stratifierade system är effektiva för att minska korskontaminering, eftersom det nästan inte finns någon omblandning i rummet, temperaturen och föroreningskoncentration ökar linjärt från värmekällan med höjden i vistelsezonen. Det finns många olika ventilationsdon som använder den stratifierade principen, såsom deplacerande ventilationsdon (DSD), impinging jet-ventilationsdon (IJSD) och väggbaserad confluent jet-ventilationsdon (WCJSD).

Huvudsyftet med denna avhandling är att analysera och jämföra olika tilluftsdon baserat på stratifierad princip i olika rumskonfigurationer med avseende på termiskt inomhusklimat, energieffektivitet och ventilationseffektivitet. Det yttersta målet är att bidra till ökad förståelse för hur ventilationssystem med olika stratifierade tilluftsdon fungerar.

Två vetenskapliga metoder har huvudsakligen använts i denna avhandling: experimentella och numeriska analyser. För numeriska analyser har CFD (Computational Fluid Dynamics) använts. De simuleringsprogram som utnyttjats för detta ändamål är ANSYS och FIDAP. Experimenten har utförts med hjälp av termoelement, varmtråds- och varmsfärsteknik, mätutrustning för termisk komfort och mätutrustning för spårgas.

Denna avhandling fokuserar framför allt på tre forskningsfrågor: interaktion mellan ett tilluftsflöde från ett deplacerande don och kallraset från ett fönster; strömningsbilden, energiprestandan och luftbyteseffektiviteten för olika tilluftsdon baserat på stratifierad ventilation; och termisk komfort för olika tilluftsdon baserade på stratifierad ventilation.

Forskningsfråga ett visade att kombinationen av tilluftsflöde genom ett deplacerande don och fönster i kallt klimat har tydlig effekt på strömningsbilden för kallraset under fönstret. Olika tilluftsflöden har en effekt på både hastigheten och temperaturen i kallraset. I detta fall minskade hastigheten med ca 9,5% och temperaturen i kallraset minskade med 0,5°C när flödeshastigheten från tilluftsdonet ökade från 10 till 15 l/s.

Forskningsfråga två visade att luftflödesmönstren mellan olika luftförsörjningssystem väsentligen var relaterade till egenskaper hos tilluftsdonen, såsom typ, konfiguration och position samt lufttillförselhastigheter och impulskraft. För WCJSD, IJSD och DSD spelade värmekällans placering, d.v.s. människor, datorer, belysning och externa värmekällor, en viktig roll vid utformningen av rummets luftflödesmönster. En intressant observation är att temperaturen i vistelsezonen är lägre och rummet har ett mer stratifierat temperaturfält, vilket innebär en effektivare ventilering av den zonen. Resultaten visade att den lägsta temperaturen i vistelsezonen uppnåddes för DSD medan IJSD och WCJSD visade en något högre temperatur, systemet med ett omblandande don (MSD) visade en påtagligt högre temperatur. Resultaten bekräftar också att luftförändringseffektiviteten (ACE) för DSD, WCJSD och IJSD ligger nära varandra. MSD visar dock i alla ingående artiklar lägre ACE än IJSD, WCJSD och DSD.

Forskningsfråga tre visade att ventilationssystem med stratifierade tilluftsdon i nästan samtliga studerade fallen haren acceptabel nivå för predicted mean vote (PPD), predicted mean vote (PMV) och percentage dissatisfied due to draft (DR). Om man jämförde ventilationssystem IJSD, WCJSD eller DSD med MSD visade det sig alltid att den termiska komforten var bättre eller på samma nivå som för MSD.

Place, publisher, year, edition, pages
Linköping: Linköping University Electronic Press, 2018. p. 87
National Category
Energy Engineering
Research subject
Sustainable Urban Development
Identifiers
urn:nbn:se:hig:diva-27909 (URN)10.3384/diss.diva-149815 (DOI)9789176852514 (ISBN)
Public defence
2018-09-14, ACAS, A-huset, Campus Valla, 10:15 (English)
Opponent
Supervisors
Available from: 2018-09-17 Created: 2018-09-17 Last updated: 2021-02-17Bibliographically approved

Open Access in DiVA

No full text in DiVA

Authority records

Cehlin, MathiasLarsson, Ulf

Search in DiVA

By author/editor
Cehlin, MathiasLarsson, Ulf
By organisation
Energy system
Energy Engineering

Search outside of DiVA

GoogleGoogle Scholar

isbn
urn-nbn

Altmetric score

isbn
urn-nbn
Total: 418 hits
CiteExportLink to record
Permanent link

Direct link
Cite
Citation style
  • apa
  • harvard-cite-them-right
  • ieee
  • modern-language-association-8th-edition
  • vancouver
  • Other style
More styles
Language
  • sv-SE
  • en-GB
  • en-US
  • fi-FI
  • nn-NO
  • nn-NB
  • de-DE
  • Other locale
More languages
Output format
  • html
  • text
  • asciidoc
  • rtf