Klimatsimulering av nybyggnation
University of Gävle, Department of Technology and Built Environment.
2008 (Swedish)Independent thesis Basic level (degree of Bachelor), 10 credits / 15 HE creditsStudent thesis
Abstract [en]

Detta examensarbete på C-nivå har genomförts i samarbete med ÅF Infrastruktur AB, Borlänge och syftar till att simulera inomhusklimatet för valda delar inom nybyggnation Experium, Lindvallen samt med hjälp av simuleringarna beräkna effekt- och energibehovet för dimensionering av en fjärrvärmeinstallation alternativt installation av elpanna samt kylcentral.

ÅF Infrastruktur AB har uppdragen installationsprojektering samt installationsledning åt beställaren Skistar som skall upprätta Experium. Vilket skall resultera i en upplevelsearena på 17 000 m2 innehållande äventyrsbad, bowlinghall, eventyta samt restauranger mm.

Författarens uppgift är att hjälpa ÅF Infrastruktur AB att klimatsimulera eventytan samt bowlinghallen på Experium med ett typiskt dygnsförlopp i beaktande. Då speciellt kolla på operativa temperaturer, relativa fuktigheter samt koldioxidnivån som uppstår i respektive lokal. För dessa simuleringar har datorprogrammet IDA Klimat & Energi 3,0 använts.

Simuleringen av ett typiskt dygnsförlopp på eventytan med 3000 personer samtidigt i lokalen på en afterski eller konsert, samt efterföljande 1500 samtidigt sittande personer skall resultera i om projekterat flöde räcker för att upprätthålla ett behagligt inomhusklimat. Simuleringen visar på att 3000 personer på samma gång är i översta laget, 1500 personer är mera realistiskt.

Simuleringen av bowlinghallen syftar till att utreda om den relativa fuktigheten som ett bowlinggolv kräver, normalt 40-50 %, upprätthålls utan befuktare under vinterhalvåret. Det visar sig att under vinterhalvåret ligger den relativa fuktigheten på 20-30 %, en befuktare krävs för att upprätthålla den relativa fuktigheten på 40-50 %.

En effekt- och energibehovsberäkning omfattande transmissions-, ventilations- och poolförluster samt energiåtgången för uppvärmning av tappvarmvatten skall tas fram som underlag för dimensionering av uppvärmningssystemet. Resultatet av dessa beräkningar blev att uppvärmningssystemet bör klara av 1,4 MW.

Simuleringar och beräkningar tas upp under kapitlet resultat och slutsats, beräkningarna återfinns sedan i bilagorna.

Abstract [en]

This diploma work has been performed in cooperation with ÅF Infrastruktur AB in Borlänge, Sweden, and aims to simulate the indoor climate for specific parts at the new erected Experium in Lindvallen. It also aims to estimate the power- and energy demand for installation of district heating or an electric boiler and a cooling centre.

ÅF Infrastruktur AB has installation planning and installation management for the orderer Skistar who shall establish Experium. Experium is an experience arena on 17 000 m2 which will comprise an adventure bath, bowling hall and restaurants etc.

The author’s assignment is to help ÅF Infrastruktur AB to simulate the climate in the “Eventytan” which is a restaurant, and the bowling hall on Experium, with consideration of a typical diurnal course and specially check out the operating temperatures, relative moisture and the carbon dioxide levels which occur in the building. This climate simulation has been carried out in the computer program IDA Indoor Climate and Energy 3,0.

The simulation of a typical diurnal course with 3000 persons at the same time in “Eventytan” and following 1500 persons shall answer the question if project supply flow will manage to sustain a pleasant indoor climate. The simulation shows that 3000 persons at the same time in “Eventytan” are slightly too much. 1500 persons is more a realistic point of view.

The simulation of the bowling hall is too investigate if the relative moisture level which the floor of bowling halls demands, normally 40-50 % to maintain without an humidifier on the winter month. The results of the simulation shows that under the winter month the relative moisture level is approximately 20-30 % which is too low, so the conclusion is that a humidifier is needed.

A power- and energy demand calculation extensive transmission-, ventilation- and pool losses also contains the energy consumption for heating hot water. This basic data underlie as decision –making for heating up the building. The result of this show a demand of 1,4 MW.

Simulations and calculations brings up under the result chapter and conclusion chapter, the calculations can be recovered back in the appendix.

Place, publisher, year, edition, pages
2008. , p. 61
Keywords [sv]
Inomhusklimat
National Category
Building Technologies
Identifiers
URN: urn:nbn:se:hig:diva-3056OAI: oai:DiVA.org:hig-3056DiVA, id: diva2:126518
Presentation
(English)
Uppsok
teknik
Supervisors
Examiners
Available from: 2009-01-13 Created: 2009-01-13Bibliographically approved

Open Access in DiVA

fulltext(929 kB)1783 downloads
File information
File name FULLTEXT01.pdfFile size 929 kBChecksum MD5
Type fulltextMimetype application/pdf

By organisation
Department of Technology and Built Environment
Building Technologies

Search outside of DiVA

GoogleGoogle Scholar
Total: 1787 downloads
The number of downloads is the sum of all downloads of full texts. It may include eg previous versions that are now no longer available

urn-nbn

Altmetric score

urn-nbn
Total: 737 hits
CiteExportLink to record
Permanent link

Direct link
Cite
Citation style
  • apa
  • harvard-cite-them-right
  • ieee
  • modern-language-association-8th-edition
  • vancouver
  • Other style
More styles
Language
  • sv-SE
  • en-GB
  • en-US
  • fi-FI
  • nn-NO
  • nn-NB
  • de-DE
  • Other locale
More languages
Output format
  • html
  • text
  • asciidoc
  • rtf