Estimates of air exchange rates (AER) in buildings are important when ventilation systems areevaluated. Many methods may be used, but here the focus lies on the PFT and CO2- methods.Traditionally, perfluorocarbon tracers (PFT) together with passive sampling has been used.However, the rise of low cost CO2- sensors has opened a relatively inexpensive route toestimating AER using the CO2 emitted by the occupants as tracer gas. The two methods havetheir different strengths and weaknesses, but are typically separated by measuring in differenttime periods. Longer periods for PFT and shorter periods for CO2.The aim here is to simultaneously measure and compare the two estimates of AER in a wellventilatedapartment during the same (short) time period. The homogeneous emission tracertechnique is used for PFT, i.e. the tracer is homogeneously emitted in all rooms of theapartment. CO2 uses the tracer emission of the occupants and usually focus on measuring thenight AER in the bedroom, but placing CO2 sensors in other positions the general AER of theapartment may be estimated. In this study the estimates of AER in the bedroom and for thewhole apartment are compared for three different bedroom door states: totally open; 1 cmopen; and closed.The PFT estimates of AER vary less with the state of the bedroom door, whereas the CO2estimates are lower (than PFT) when the door is open and progressively higher (than PFT)when the door is more closed.