Experimental and numerical study of corner impinging jet ventilation for an office environment
University of Gävle, Faculty of Engineering and Sustainable Development, Department of Building Engineering, Energy Systems and Sustainability Science, Energy Systems and Building Technology.ORCID iD: 0000-0002-8349-6659
2024 (English)Doctoral thesis, comprehensive summary (Other academic)
Abstract [en]

An effective ventilation system is an important component of a building’s service infrastructure. It serves the dual purpose of creating a comfortable and healthy indoor environment for occupants, thereby enhancing their well-being and productivity. However, the ventilation system is also a part of the building that uses a high amount of energy.

The main objective of this study is to evaluate a novel implementation of the impinging jet ventilation system by placing the supply inlet at the corners of the space or room, rather than in the traditional mid-wall section. The focus of this study is to test and evaluate corner impinging jet ventilation in a medium-sized office environment within a building that requires moderate amount of heating and cooling.

In the first part of this study (summer condition), the system is evaluated in an experimental environment, where it is compared against other systems such as displacement ventilation and mixing ventilation. The evaluated parameters indicates that corner impinging ventilation system performs better than mixing ventilation but show similar results to displacement ventilation in terms of airchange effectiveness. This experimental setup was also tested in winter condition and the results showed that the system was most effective during summertime compared to wintertime. In wintertime the results for the air change effectiveness were similar to those of a mixing system.

In the second part, numerical simulations were utilized to delve deeper into the behaviour of the corner impinging jet ventilation system close to the floor surface. A numerical model was created and validated against experimental measurements. In this part, the spreading of the air jet across the room floor was examined, and its relation to various parameters such as inlet velocity, inlet shape and discharge height. Results indicated that diffuser geometries have almost no impact on velocity profile along the floor's centreline, jet spreading rate and maximum velocity decay. The results also showed a high degree of flexibility for the room size, between 25-100 m2 for which the results were applicable. The results also concluded that there was a noticeable confinement effect present and that the jet was able to travel far into the room.

In the third part numerical simulations was used for validating and to create a model for an office room containing two office workstations. The office room was evaluated in terms of local thermal comfort, close to the sitting area. In addition, the indoor air quality was also examined. The results showed that corner impinging ventilation system performed better than conventional mixing ventilation system, especially when evaluating the indoor air quality in terms of mean age of air. This evaluation also took into account both outdoor summer and winter conditions, as well as different inlet surface areas. Different locations for the workstations were also evaluated with good results, except for placing the work-stations close to the inlets. Due to the system’s effectiveness of providing fresh air to the occupants, further analysis was made to try and reduce the air flowrate but keep the same indoor air quality level as an equivalent fully mixing ventilation system. By using this method, the study was able to demonstrate reduction in the energy use by reducing the air flowrate of the supply inlet. The study showed a possible reduction of the energy use by 7-9 % for outdoor temperatures ranging between -15 °C to 25 °C.

Abstract [sv]

Ett effektivt ventilationssystem är en viktig komponent i en byggnads serviceinfrastruktur. Den tjänar det dubbla syftet att skapa en bekväm och hälsosam inomhusmiljö för de boende, därigenom förbättrande deras välbefinnande och produktivitet. Dock är ventilationssystemet också en del av byggnaden som använder en hög andel energi.

Den huvudsakliga målsättningen med denna studie är att utvärdera en ny implementering av impinging jet ventilationssystem genom att placera inloppen i hörnen av rummet, i stället för den traditionella mellanväggsektionen. Fokus för denna studie är att testa och utvärdera corner impinging jet ventilation (CIJV) i en medelstor kontorsmiljö i en byggnad som kräver måttlig uppvärmning och kylning.

I den första delen av denna studie utvärderas systemet i en experimentell miljö, där det jämförs med andra system såsom deplacerade ventilation och omblandad ventilation för sommar fall. De utvärderade parametrarna indikerar att CIJV presterar bättre än omblandad ventilation men visar liknande resultat som deplacerad ventilationssystem när det gäller luftväxlingseffektivitet. Denna experimentella uppställning testades också under vinterförhållanden och resultaten visade att systemet var mest effektivt under sommartiden jämfört med vintertiden. Under vintertiden var resultaten för luftväxlingseffektiviteten liknande de för omblandande ventilationssystem.

I den andra delen användes numeriska simuleringar för att fördjupa förståelsen av CIJVs beteende nära golvytan. En numerisk modell skapades och validerades mot experimentella mätningar. I den här delen granskades spridningen av luftstrålen över golvet och dess relation till olika parametrar som tilluftshastighet, ventilationsdonet geometri och ventilationsdonets höjd över golvytan. Resultaten indikerade att ventilationsdonet geometri har en marginell inverkan på hastighetsutvecklingen längs golvvägens mittlinje, maximal hastighetsminskning och strålens spridningshastighet. Resultaten visade också en hög grad av flexibilitet när det gäller rumsstorlek, mellan 25–100m2 för vilka resultaten var tillämpliga. Resultaten konstaterade också att det fanns en märkbar restriktionseffekt närvarande och att strålen kunde färdas långt in i rummet.

I den tredje delen användes numeriska simuleringar i en kontorsmiljö med två arbetsstationer. Kontorsrummet utvärderades både när det gällde den lokaltermisk komforten och luftkvalitén inomhus. Resultaten visade att CIJV presterade bättre än ett konventionellt omblandande system, särskilt när man utvärderade luftkvalitén med avseende på luftens medelålder. Utvärderingen beaktade också både utomhusförhållanden på sommaren och vintern samt olika flödeshastigheter. Olika platser för arbetsstationerna utvärderades också med goda resultat, förutom att när arbetsstationerna placerades nära inloppen.

På grund av systemets effektivitet när det gäller att förse frisk luft till kontorsarbetarna gjordes en ytterligare analys för att försöka minska luftflödet men behålla samma nivå av luftkvalitén som ett motsvarande omblandande system. Genom att använda denna metod kunde studien visa på en minskning i energiförbrukningen genom att minska luftflödet för tilluften med 7-9 % för utomhustemperaturer som sträckte sig från -15 °C till 25 °C.

Place, publisher, year, edition, pages
Gävle: Gävle University Press , 2024. , p. 87
Series
Doctoral thesis ; 47
Keywords [en]
corner impinging jet, ventilation, thermal comfort, mean age of air, indoor air quality
Keywords [sv]
corner impinging jet, ventilation, termisk komfort, genomsnittslig luftålder, inomhusluftkvalitet
National Category
Energy Systems
Identifiers
URN: urn:nbn:se:hig:diva-44058ISBN: 978-91-89593-34-3 (print)ISBN: 978-91-89593-35-0 (electronic)OAI: oai:DiVA.org:hig-44058DiVA, id: diva2:1851420
Public defence
2024-06-14, 12:108, Kungsbäcksvägen 47, Gävle, 09:00
Opponent
Supervisors
Available from: 2024-05-22 Created: 2024-04-15 Last updated: 2025-10-02Bibliographically approved
List of papers
1. Experimental investigation of ventilation performance of different air distribution systems in an office environment – cooling mode
Open this publication in new window or tab >>Experimental investigation of ventilation performance of different air distribution systems in an office environment – cooling mode
2019 (English)In: Energies, E-ISSN 1996-1073, Vol. 12, no 7, article id 1354Article in journal (Refereed) Published
Abstract [en]

The performance of a newly designed corner impinging jet air distribution method with an equilateral triangle cross section was evaluated experimentally and compared to that of two more traditional methods (mixing and displacement ventilation). At nine evenly chosen positions with four standard vertical points, air velocity, turbulence intensity, temperature, and tracer gas decay measurements were conducted for all systems. The results show that the new method behaves as a displacement ventilation system, with high air change effectiveness and stratified flow pattern and temperature field. Both local air change effectiveness and air exchange effectiveness of the corner impinging jet showed high quality and promising results, which is a good indicator of ventilation effectiveness. The results also indicate that there is a possibility to slightly lower the airflow rates for the new air distribution system, while still meeting the requirements for thermal comfort and indoor air quality, thereby reducing fan energy usage. The draught rate was also lower for corner impinging jet compared to the other tested air distribution methods. The findings of this research show that the corner impinging jet method can be used for office ventilation.

Place, publisher, year, edition, pages
MDPI, 2019
Keywords
Corner impinging jet, mixing ventilation, displacement ventilation, tracer gas, air exchange effectiveness, air change effectiveness, draught rate
National Category
Energy Engineering
Research subject
Sustainable Urban Development
Identifiers
urn:nbn:se:hig:diva-29443 (URN)10.3390/en12071354 (DOI)000465561400171 ()2-s2.0-85065464428 (Scopus ID)
Available from: 2019-04-05 Created: 2019-04-05 Last updated: 2025-10-02Bibliographically approved
2. Experimental Investigation of Ventilation Performance of Different Air Distribution Systems in an Office Environment: Heating Mode
Open this publication in new window or tab >>Experimental Investigation of Ventilation Performance of Different Air Distribution Systems in an Office Environment: Heating Mode
2019 (English)In: Energies, E-ISSN 1996-1073, Vol. 12, no 10, article id 1835Article in journal (Refereed) Published
Abstract [en]

A vital requirement for all-air ventilation systems are their functionality to operate both in cooling and heating mode. This article experimentally investigates two newly designed air distribution systems, corner impinging jet (CIJV) and hybrid displacement ventilation (HDV) in comparison against a mixing type air distribution system. These three different systems are examined and compared to one another to evaluate their performance based on local thermal comfort and ventilation effectiveness when operating in heating mode. The evaluated test room is an office environment with two workstations. One of the office walls, which has three windows, faces a cold climate chamber. The results show that CIJV and HDV perform similar to a mixing ventilation in terms of ventilation effectiveness close to the workstations. As for local thermal comfort evaluation, the results show a small advantage for CIJV in the occupied zone. Comparing C2-CIJV to C2-CMV the average draught rate (DR) in the occupied zone is 0.3% for C2-CIJV and 5.3% for C2-CMV with the highest difference reaching as high as 10% at the height of 1.7 m. The results indicate that these systems can perform as well as mixing ventilation when used in offices that require moderate heating. The results also show that downdraught from the windows greatly impacts on the overall airflow and temperature pattern in the room.

Keywords
Corner impinging jet, mixing ventilation, displacement ventilation, tracer gas, air exchange effectiveness, air change effectiveness, draught rate
National Category
Energy Systems
Research subject
Sustainable Urban Development
Identifiers
urn:nbn:se:hig:diva-29582 (URN)10.3390/en12101835 (DOI)000471016700014 ()2-s2.0-85066877057 (Scopus ID)
Available from: 2019-05-21 Created: 2019-05-21 Last updated: 2025-10-02Bibliographically approved
3. Numerical investigation of the flow behavior of an isothermal corner impinging jet for building ventilation
Open this publication in new window or tab >>Numerical investigation of the flow behavior of an isothermal corner impinging jet for building ventilation
Show others...
2022 (English)In: Building and Environment, ISSN 0360-1323, E-ISSN 1873-684X, Vol. 223, article id 109486Article in journal (Refereed) Published
Abstract [en]

The corner impinging jet concept has been proposed as a new air distribution system for use in office environments. The present paper reports the mean flow field behavior of an isothermal corner-based turbulent impinging jet in a room. A detailed experimental study is carried out to validate the numerical simulations, and the predictions are performed using three turbulence models. RNG k−ε model was chosen for this study. This study investigates the influence different configuration parameters such as jet discharge height, diffuser geometry (shape and size) and supply airflow rate have on the flow field. The results show that the diffuser geometries used in this study had in general a minor effect on the velocity developments along the centerline of the floor, maximum velocity decay and jet spreading rate except for some specific cases. When evaluating the triangle geometry cases, the results show that all the cases with volume flow <20 L/s are able to meet Boverket's building regulations velocity requirement both for summer and winter. The applicability evaluation show that the results can be considered for room sizes between ≈25 and 100 m2. In addition, the wall confinement effect (90° vs. 180°) is having a significant impact on the maximum velocity decay for corner impinging jet ventilation. In the regression analysis the results shows that the distance along the diagonal centerline of the room has the most impact on the evaluation of maximum velocity decay and jet spreading rate.

Place, publisher, year, edition, pages
Elsevier, 2022
Keywords
Impinging jet ventilation; CFD analysis; Parametric study; Regression analysis
National Category
Fluid Mechanics
Research subject
Sustainable Urban Development
Identifiers
urn:nbn:se:hig:diva-39687 (URN)10.1016/j.buildenv.2022.109486 (DOI)000849946600004 ()2-s2.0-85136053893 (Scopus ID)
Available from: 2022-08-14 Created: 2022-08-14 Last updated: 2025-10-02Bibliographically approved
4. Energy saving, indoor thermal comfort and indoor air quality evaluation of an office environment using corner impinging jet ventilation
Open this publication in new window or tab >>Energy saving, indoor thermal comfort and indoor air quality evaluation of an office environment using corner impinging jet ventilation
Show others...
2023 (English)In: Developments in the Built Environment, ISSN 2666-1659, Vol. 15, article id 100179Article in journal (Refereed) Published
Abstract [en]

The performance of a corner based impinging jet ventilation system (CIJV) in an office environment was evaluated numerically. The evaluation was done both in terms of the local thermal comfort and the local indoor air quality. Three different inlet configurations were tested for a range of outdoor temperatures that included both winter and summer conditions. In terms of indoor air quality, the results showed that CIJV performed better than a traditional mixing system. The study also revealed that CIJV creates a stronger temperature stratification in summertime compared to wintertime. When evaluating the energy saving potential the results showed a possible reduction of 7% for the ventilation flowrate when the outdoor temperatures were between -15 °C and -5 °C, 8 % when the outdoor temperatures were between 0 °C and 10 °C and 9 % when the outdoor temperatures were between 15 °C and 25 °C.

Place, publisher, year, edition, pages
Elsevier, 2023
Keywords
Corner impinging jet ventilation, Computational fluid dynamic, Thermal comfort, Indoor air quality, Energy saving
National Category
Energy Systems
Research subject
Sustainable Urban Development
Identifiers
urn:nbn:se:hig:diva-41938 (URN)10.1016/j.dibe.2023.100179 (DOI)001054802900001 ()2-s2.0-85161659218 (Scopus ID)
Available from: 2023-06-02 Created: 2023-06-02 Last updated: 2025-10-02Bibliographically approved
5. Numerical investigation of indoor thermal comfort and air quality for an office equipped with corner impinging jet ventilation
Open this publication in new window or tab >>Numerical investigation of indoor thermal comfort and air quality for an office equipped with corner impinging jet ventilation
2023 (English)In: Advances in Building Energy Research, ISSN 1751-2549, E-ISSN 1756-2201, Vol. 17, no 5, p. 578-604Article in journal (Refereed) Published
Abstract [en]

This study investigates the feasibility of using only corner impinging jet ventilation (CIJV) for heating and cooling a medium-sized office space with two occupants while maintaining adequate indoor thermal comfort and air quality compared to traditional mixing ventilation systems. This study examines what impact various outdoor temperatures, ranging from −15°C to 25°C, have on an office environment in terms of indoor thermal comfort and air quality. Three different workspace positions were evaluated. The results show that the CIJV system meets the ASHRAE thermal comfort standards for all three positions. In terms of indoor air quality, CIJV performs better than traditional mixing systems, with improved mean age of air and ACE values. This study concludes that CIJV can be used both close and far away from the supply inlets and still provide adequate indoor thermal comfort and air quality during both cooling and heating season.

Place, publisher, year, edition, pages
Taylor & Francis, 2023
Keywords
corner impinging jet ventilation, heating and cooling, computational fluid dynamic, thermal comfort, indoor air quality
National Category
Energy Systems
Research subject
Sustainable Urban Development
Identifiers
urn:nbn:se:hig:diva-43137 (URN)10.1080/17512549.2023.2269925 (DOI)001088045800001 ()2-s2.0-85174303303 (Scopus ID)
Available from: 2023-10-17 Created: 2023-10-17 Last updated: 2025-10-02Bibliographically approved

Open Access in DiVA

fulltext(2204 kB)297 downloads
File information
File name FULLTEXT02.pdfFile size 2204 kBChecksum SHA-512
0e522c059b09681c6c0fb5fda00aa17d24b39ccb5c9491180cb847bfd8af361ed2695bd4e1b9de0de666b9337b9bcb36d1e94cbcd110db870e51c960f336039b
Type fulltextMimetype application/pdf

Authority records

Ameen, Arman

Search in DiVA

By author/editor
Ameen, Arman
By organisation
Energy Systems and Building Technology
Energy Systems

Search outside of DiVA

GoogleGoogle Scholar
Total: 300 downloads
The number of downloads is the sum of all downloads of full texts. It may include eg previous versions that are now no longer available

isbn
urn-nbn

Altmetric score

isbn
urn-nbn
Total: 1365 hits
CiteExportLink to record
Permanent link

Direct link
Cite
Citation style
  • apa
  • harvard-cite-them-right
  • ieee
  • modern-language-association-8th-edition
  • vancouver
  • Other style
More styles
Language
  • sv-SE
  • en-GB
  • en-US
  • fi-FI
  • nn-NO
  • nn-NB
  • de-DE
  • Other locale
More languages
Output format
  • html
  • text
  • asciidoc
  • rtf