hig.sePublications
Change search
CiteExportLink to record
Permanent link

Direct link
Cite
Citation style
  • apa
  • harvard-cite-them-right
  • ieee
  • modern-language-association-8th-edition
  • vancouver
  • Other style
More styles
Language
  • sv-SE
  • en-GB
  • en-US
  • fi-FI
  • nn-NO
  • nn-NB
  • de-DE
  • Other locale
More languages
Output format
  • html
  • text
  • asciidoc
  • rtf
Indoor Temperature Response Under Natural Circulation Scenarios During Winter Power Outage in District-Heating-Connected Buildings
University of Gävle, Faculty of Engineering and Sustainable Development, Department of Building Engineering, Energy Systems and Sustainability Science, Energy Systems and Building Technology.
2026 (English)Independent thesis Advanced level (degree of Master (Two Years)), 10 credits / 15 HE creditsStudent thesis
Abstract [en]

Natural circulation is a passive heat-transfer mechanism that may partially sustain space heating in district-heating-connected buildings under power outages, with field observations reporting significant variability in the levels achieved. This study simulates the indoor temperature response under natural circulation conditions during a 14-day winter outage in two district heating-connected buildings in Smedjebacken, Sweden, in which the phenomenon was previously identified in field experiments. Building A is a Miljonprogrammet multifamily building constructed in 1965, and Building B is an elderly home constructed in 1991. Both buildings were modeled in IDA ICE as multizone models, with five natural circulation levels assumed at the heat exchanger: NC 0%, NC 20%, NC 40%, NC 60% and NC 80%. Two climate profiles were developed, Winter and Severe Winter with mean outdoor temperature at -1 °C and -13 °C, respectively. A third condition, Winter with Severe Winter Heating Capacity, was also simulated, aiming to explore an upper range of natural circulation performance. Indoor temperatures were monitored against two thresholds, 15 °C as an indicative threshold for occupant safety and 5 °C for building structural integrity. The heat supply was distributed across zones based on an assumed spatial loss distribution of 5% per approximately 10 meters from the heat exchanger and an additional 5% per floor above.

The results show that NC 80% and NC 60% at the heat exchanger maintained indoor temperatures above 15 °C in the majority of the zones throughout the outage period under all climate conditions. NC 40% represented an intermediate response, with considerable variation across zones and climate conditions. NC 20% provided a contribution limited to zones closest to the heat exchanger, with performance comparable to NC 0% in intermediate and distant zones. The range from NC 20% to NC 40% at the heat exchanger was identified as a transition band, with occurrences reported in natural circulation field tests in the literature, and representing the interval between negligible and meaningful thermal protection across the building for both indoor temperature and additional days before the assumed thresholds are crossed.

The study contributes an apartment-level perspective on the thermal response under reduced heat supply conditions, shifting the typical focus of natural circulation from the heat exchanger to the indoor environment.

Place, publisher, year, edition, pages
2026. , p. 51
Series
Research report
Keywords [en]
Natural Circulation, Indoor Temperature, Power Outages, IDA ICE, District Heating.
National Category
Energy Systems
Identifiers
URN: urn:nbn:se:hig:diva-50525OAI: oai:DiVA.org:hig-50525DiVA, id: diva2:2080471
Educational program
Energy engineering – master’s programme online (one year) (in eng)
Presentation
2026-06-12, 10:30 (English)
Supervisors
Examiners
Available from: 2026-06-30 Created: 2026-06-26 Last updated: 2026-06-30Bibliographically approved

Open Access in DiVA

fulltext(2960 kB)48 downloads
File information
File name FULLTEXT01.pdfFile size 2960 kBChecksum SHA-512
aefda47e88ab540db509f5e45aff43a345ac2fbf783be60e68ef5b3eb0b24170d772f5f7719aa2a732735e9d5d6115cd03f5b0cd6a39b8ef6e4cd4ef7e0d6835
Type fulltextMimetype application/pdf

By organisation
Energy Systems and Building Technology
Energy Systems

Search outside of DiVA

GoogleGoogle Scholar
Total: 48 downloads
The number of downloads is the sum of all downloads of full texts. It may include eg previous versions that are now no longer available

urn-nbn

Altmetric score

urn-nbn
Total: 138 hits
CiteExportLink to record
Permanent link

Direct link
Cite
Citation style
  • apa
  • harvard-cite-them-right
  • ieee
  • modern-language-association-8th-edition
  • vancouver
  • Other style
More styles
Language
  • sv-SE
  • en-GB
  • en-US
  • fi-FI
  • nn-NO
  • nn-NB
  • de-DE
  • Other locale
More languages
Output format
  • html
  • text
  • asciidoc
  • rtf