A new air supply terminal based on confluent jets was installed on a workbench, in vicinity of a CNC machine, of an industrial space. The flow pattern and temperature field was carried out by CFD calculations and infrared camera imaging technique. A main goal of this technique is to save energy therefore the jet should distribute the air where it is desired. This is possible because the confluent jets system uses the benefits of both mixing (high momentum for better spreading of the air jet) and displacement (cleaner air in occupied zone). The results show that thermal comfort and air quality analysis relies on consistent facts and is in good agreements with the existed standards. It was shown that the supply terminal is able to spread the fresh air to the needed work area. This is an advantage of the high momentum air distribution system used in this investigation.